How to Size a Refrigerated Air Dryer for Your Air Compressor

WhatsApp

+86 180 5167 0936

Product Specifications

To size a refrigerated air dryer, find the highest airflow that will pass through the dryer and check the candidate model’s capacity at your operating conditions. A dryer rated for 15 m³/min may treat less than 15 m³/min in a hot compressor room. Use the manufacturer’s correction tables to check the usable capacity before ordering.

1. Find the maximum airflow through the dryer

For one compressor feeding one dryer, start with the compressor’s free air delivery (FAD) at the working pressure. For two or more compressors feeding one dryer, add the flows of the units that can run and feed that dryer at the same time. For example, two 6 m³/min compressors feeding a shared dryer can send up to 12 m³/min through it.

Verify the reference conditions before comparing FAD, SCFM and Nm³/min. Ask the supplier to put compressor delivery and dryer capacity on the same reference basis. Compressor motor power alone cannot establish airflow.

2. Record pressure and temperatures at the dryer

  • Inlet pressure: Provide the normal and minimum operating pressure at the dryer inlet, with the units and whether the reading is gauge or absolute.
  • Compressed-air inlet temperature: Measure or estimate the highest temperature after the aftercooler, at the dryer connection.
  • Cooling conditions: For an air-cooled dryer, use the highest temperature at the condenser air intake. For a water-cooled unit, provide the available cooling-water temperature and flow.

Check that the proposed model stays within its operating limits throughout the expected duty. A sizing correction cannot make a model suitable for a condition outside those limits.

3. Specify the required pressure dew point

Pressure dew point is the temperature at which water vapor begins to condense at the stated air pressure. Check the coldest downstream pipe or use point when setting the target. If the process needs a sub-zero pressure dew point, compare desiccant air dryers and confirm the required moisture specification with your supplier.

4. Worked example: can a 15 m³/min dryer handle 12 m³/min?

Assume the maximum treated flow is 12 m³/min on the same reference basis as the dryer rating. The dryer inlet is 7 bar(g) and 45°C, the condenser intake is 35°C, and the required pressure dew point is +5°C.

Suppose the candidate model’s manufacturer gives a combined capacity multiplier of 0.80 for those conditions. A dryer rated for 15 m³/min at catalog conditions would then have a usable capacity of 15 × 0.80 = 12 m³/min. It just meets the design flow, with zero reserve. If your project allows for a future increase to 13.2 m³/min, the minimum catalog rating under the same multiplier would be 13.2 ÷ 0.80 = 16.5 m³/min. Check the next available model using its own data.

The 0.80 multiplier is illustrative and is not an SMD correction factor. Some manufacturers instead supply factors that multiply the required flow for catalog selection. Follow the calculation printed with the model’s table. Reference on dryer sizing and correction factors.

5. Check the model before you order

Confirm the outlet pressure dew point, pressure drop at design flow, cooling requirements, electrical supply, pipe connections and condensate drain arrangement. If the dryer serves several lines, tell the supplier which compressors can operate together and whether you plan to add capacity.

The SUPERMAN SMD refrigerated air dryer catalog lists air-cooled capacities of 1.6–100 Nm³/min and water-cooled capacities of 20–400 Nm³/min. These are series ranges at catalog conditions. Use the model’s correction data to confirm capacity at your site. For dryers and filters as a treatment train, see our compressed-air treatment selection guide.

Need a model recommendation? Send your maximum airflow, minimum inlet pressure, maximum inlet and cooling temperatures, and target pressure dew point. Request an SMD sizing review and quote.